Free Voltage Drop Calculator

Voltage Drop Calculator

Calculate voltage drop in volts and percent for copper or aluminum wire, single-phase or three-phase, and find the smallest wire size that stays under the NEC 3% and 5% recommendations.

NEC 2023 Chapter 9 Table 8 resistance
14 AWG to 500 kcmil
Feet or meters

Voltage Drop & Wire Size Calculator

Enter the one-way length from the source to the load. The calculator doubles it for the return path.

Calculator inputs

Single-phase: the circuit voltage. Three-phase: the line-to-line voltage.

Source to load along the actual route, not a straight line. Do not double it; the formula does.

Planning estimate only. Confirm field measurements, product coverage, local requirements, waste, pricing, and supplier quantities before ordering or bidding.

The 3% and 5% limits are recommendations, not requirements

NEC 2023 210.19(A) Informational Note No. 4 (branch circuits) and 215.2(A)(1) Informational Note No. 2 (feeders) describe conductors sized for no more than 3% drop at the farthest outlet, and no more than 5% for feeder and branch circuit combined, as providing reasonable efficiency of operation. Under NEC 2023 90.5(C), informational notes are not enforceable. Your jurisdiction, an energy code, or the project specification may still make a limit mandatory.

Worked Example: 120 V, 20 A, 150 ft of 12 AWG Copper

A 20 A, 120 V single-phase circuit runs 150 feet one-way to a detached shop on 12 AWG stranded copper. NEC 2023 Chapter 9 Table 8 lists 12 AWG uncoated stranded copper at 1.98 ohms per 1,000 feet at 75°C.

  1. Voltage dropVD = 2 × I × R × L / 1,000 = 2 × 20 × 1.98 × 150 / 1,000 = 11.88 V
  2. Percent drop11.88 / 120 × 100 = 9.9%
  3. Voltage at the load120 − 11.88 = 108.12 V
  4. K-factor check2 × 12.9 × 20 × 150 / 6,530 cmil = 11.85 V (9.88%)
  5. Size for 3% (3.6 V)R ≤ 3.6 × 1,000 / (2 × 20 × 150) = 0.60 Ω/1,000 ft → 6 AWG (0.491)
  6. Size for 5% (6.0 V)R ≤ 6.0 × 1,000 / (2 × 20 × 150) = 1.00 Ω/1,000 ft → 8 AWG (0.778)

At 9.9%, 12 AWG is well over both recommendations. 8 AWG brings the drop to 4.67 V (3.89%), within the combined 5% figure; 6 AWG brings it to 2.95 V (2.46%), within 3%. Upsizing for voltage drop does not change the 20 A overcurrent protection. If a wire-type equipment grounding conductor is installed, NEC 2023 250.122(B) requires it to be increased in proportion, and larger conductors may need pigtails at devices, a larger box, or a larger raceway.

Wire Size, Circular Mils, and Resistance Table

Values from NEC 2023 Chapter 9, Table 8 (Conductor Properties): conductor area in circular mils and DC resistance at 75°C in ohms per 1,000 feet, uncoated copper and aluminum. The calculator uses the stranded values. Table 8 also lists 14–8 AWG as solid conductors, shown in brackets.

SizeArea (cmil)Copper Ω/1,000 ftAluminum Ω/1,000 ft
14 AWG4,1103.14 [3.07]5.17 [5.06]
12 AWG6,5301.98 [1.93]3.25 [3.18]
10 AWG10,3801.24 [1.21]2.04 [2]
8 AWG16,5100.778 [0.764]1.28 [1.26]
6 AWG26,2400.4910.808
4 AWG41,7400.3080.508
3 AWG52,6200.2450.403
2 AWG66,3600.1940.319
1 AWG83,6900.1540.253
1/0 AWG105,6000.1220.201
2/0 AWG133,1000.09670.159
3/0 AWG167,8000.07660.126
4/0 AWG211,6000.06080.1
250 kcmil250,0000.05150.0847
300 kcmil300,0000.04290.0707
350 kcmil350,0000.03670.0605
400 kcmil400,0000.03210.0529
500 kcmil500,0000.02580.0424

AC resistance and reactance for conductors in PVC, aluminum, and steel conduit are in NEC 2023 Chapter 9, Table 9. Check the edition your jurisdiction has adopted; confirm values against the printed code.

How Far Can You Run Copper Wire?

Longest one-way run, in feet, before single-phase voltage drop reaches 3% or 5%, calculated from the Table 8 stranded copper resistance with the full current flowing to the end of the run. Less current means a longer allowable run in direct proportion.

Copper size and load120 V at 3%120 V at 5%240 V at 3%240 V at 5%
14 AWG at 15 A38 ft63 ft76 ft127 ft
12 AWG at 20 A45 ft75 ft90 ft151 ft
10 AWG at 30 A48 ft80 ft96 ft161 ft
8 AWG at 40 A57 ft96 ft115 ft192 ft
6 AWG at 50 A73 ft122 ft146 ft244 ft

Example loads only, not ampacity ratings. Size every conductor for ampacity and overcurrent protection under NEC 2023 310.16 and 240.4(D) first, then check voltage drop.

How to Measure Run Length

Voltage drop is directly proportional to length, so a 20% error in the run is a 20% error in the answer. Measure the path the conductors will take, from the panel, transformer, or source to the farthest outlet or load on the circuit.

  • Follow the route, not the straight line. Conduit and cable run along walls, through joists, and around obstructions. On a plan, trace the homerun and each leg at the drawing scale.
  • Add the vertical runs. Include the drop from the ceiling or the rise from the slab to each device, and the rise into the panel.
  • Add slack. Allow for the conductor left in boxes, panels, and at the equipment for terminations.
  • Enter it one way. The single-phase formula doubles the length for the return conductor; three-phase uses √3.
  • Check the whole path. For a subpanel, calculate the feeder and the longest branch circuit separately and add the two percentages.

Automate your electrical takeoffs and quotes.

Size the long runs here, then get more electrical quotes out with less time measuring and counting on PDF plans. BuildVision extracts counts and measurements from your plans and carries them through your rates and assemblies into a branded quote. Your team checks the quantities and pricing before sending. Try it free on your own plans.

How the Voltage Drop Calculator Works

Every conductor has resistance, so part of the source voltage is used up pushing current down the wire and back. On a 120 V circuit carrying 20 A through 150 feet of 12 AWG copper, that loss is 11.88 V, or 9.9 percent, leaving 108.12 V at the load. This calculator works that out for copper or aluminum conductors from 14 AWG to 500 kcmil, single-phase or three-phase, and then finds the smallest size that keeps the drop at or below 3 percent and 5 percent.

The 3 and 5 percent figures come from the National Electrical Code. NEC 2023 210.19(A) Informational Note No. 4 (branch circuits) and 215.2(A)(1) Informational Note No. 2 (feeders) say that conductors sized to keep voltage drop to no more than 3 percent at the farthest outlet, with no more than 5 percent on the feeder and branch circuit combined, provide reasonable efficiency of operation. Informational notes are explanatory material, not enforceable requirements (NEC 2023 90.5(C)), so treat these as design recommendations unless your jurisdiction, an energy code, or the project specification makes them mandatory.

By default the calculator uses the DC resistance at 75°C from NEC 2023 Chapter 9, Table 8 (Conductor Properties), stranded uncoated copper or aluminum. You can switch to the K-factor shortcut (K = 12.9 for copper, 21.2 for aluminum) to match hand calculations and exam-style answers; the two methods agree within a few percent. Voltage drop is only one sizing check: the conductor must also carry the load under the ampacity rules of NEC 2023 310.16 and the small-conductor limits of 240.4(D).

Voltage drop formulas (one-way length L in feet)

  • Single-phase: VD = 2 × I × R × L / 1,000 (R = ohms per 1,000 ft from NEC Ch. 9 Table 8)
  • Three-phase: VD = √3 × I × R × L / 1,000 (√3 ≈ 1.732, line-to-line voltage)
  • K-factor shortcut, single-phase: VD = 2 × K × I × L / CM
  • K-factor shortcut, three-phase: VD = √3 × K × I × L / CM (K = 12.9 copper, 21.2 aluminum)
  • Percent drop = VD / source voltage × 100; voltage at load = source voltage − VD
  • Smallest size for a target: CM ≥ 2 × K × I × L / (target % × V / 100) (use √3 for three-phase)

Estimating Steps and Checks

1

Identify the circuit

Note the conductor material, the source voltage, and whether the circuit is single-phase or three-phase. For three-phase circuits use the line-to-line voltage, such as 208 V or 480 V. For a 277 V lighting circuit fed from a 480Y/277 V panel, the circuit is single-phase at 277 V.

2

Measure the one-way run length

Measure from the panel or source to the farthest outlet or load along the route the wire will actually take, not a straight line. On a scaled plan, trace the homerun and circuit path, then add the vertical drops from ceiling to device height, rises up walls, and slack at boxes and panels. Enter the one-way distance; the formula doubles it for the return conductor.

3

Enter the load current

Use the calculated or nameplate load current that will flow at the far end. Using the breaker rating instead gives a conservative result. For a circuit that feeds several loads along its length, the drop calculated with the full current at the farthest point is the worst case.

4

Compare the result and upsize if needed

Read the percent drop against the 3 percent branch-circuit and 5 percent combined recommendations. If the run is over, choose the smallest size the calculator lists for your target, then confirm that size also meets ampacity, overcurrent protection, termination temperature ratings, and box and conduit fill.

Common Checks

  • Ampacity check: a size that passes for voltage drop must still meet NEC 2023 310.16 ampacity and the 240.4(D) small-conductor overcurrent limits. Voltage drop never allows a smaller wire than ampacity requires.
  • Combined drop check: the 5 percent figure is the total from the service or source to the farthest outlet. If the feeder already drops 2 percent, the branch circuit has about 3 percent left.
  • Length check: enter one-way length only. Doubling the run yourself and then using the single-phase formula counts the return path twice and doubles the answer.
  • Large conductor check: Table 8 is DC resistance. For 1/0 and larger conductors, especially in steel conduit, AC resistance and reactance in NEC 2023 Chapter 9 Table 9 can give a different result; use Table 9 or the manufacturer data for large feeders.
  • Mandatory limit check: some articles set enforceable limits. NEC 2023 647.4(D) limits voltage drop on sensitive electronic equipment branch circuits to 1.5 percent and the feeder plus branch circuit to 2.5 percent.

Voltage Drop Calculator FAQs

What is acceptable voltage drop?

The common target is 3 percent or less on a branch circuit at the farthest outlet and 5 percent or less for the feeder and branch circuit combined. Those figures come from NEC 2023 210.19(A) Informational Note No. 4 and 215.2(A)(1) Informational Note No. 2. They are recommendations, not code requirements, unless an energy code, local amendment, or the project specification adopts them.

How far can you run 12 gauge wire on 20 amps?

On a 120 V single-phase circuit with a full 20 A load, 12 AWG stranded copper (1.98 ohms per 1,000 ft in NEC Chapter 9 Table 8) reaches 3 percent drop at about 45 feet one-way and 5 percent at about 76 feet. At 16 A, the 3 percent distance is about 57 feet. On a 240 V circuit the same wire goes about twice as far: roughly 91 feet at 3 percent and 152 feet at 5 percent with 20 A.

Does voltage drop matter on 240 V?

Yes, but it matters less as a percentage. The same wire, current, and length lose the same number of volts at 240 V as at 120 V, so the percentage is half. 150 feet of 12 AWG copper at 20 A drops 11.88 V either way: 9.9 percent of 120 V, but 4.95 percent of 240 V.

Copper vs aluminum: how different is the voltage drop?

Aluminum has about 1.6 times the resistance of copper of the same size in NEC Chapter 9 Table 8 (for example 0.201 versus 0.122 ohms per 1,000 ft at 1/0 AWG), so it drops about 1.6 times the voltage. To match copper, aluminum usually has to be about two AWG sizes larger: 1/0 aluminum (0.201) is close to 2 AWG copper (0.194).

What is the formula for voltage drop?

Single-phase voltage drop is 2 × I × R × L / 1,000, where I is current in amps, R is the conductor resistance in ohms per 1,000 feet, and L is the one-way length in feet. Three-phase replaces the 2 with √3 (about 1.732) and uses line-to-line voltage. The K-factor form is 2 × K × I × L / CM, with K = 12.9 for copper, K = 21.2 for aluminum, and CM the conductor area in circular mils.

Where do the K values 12.9 and 21.2 come from?

K is the resistance of a conductor one circular mil in area and one foot long, in ohms, at operating temperature. Multiplying a Table 8 resistance by its area gives about the same number: 1.98 ohms per 1,000 ft × 6,530 circular mils for 12 AWG copper is about 12.9. The shortcut is handy for hand calculations; the tabulated resistance is slightly more precise for each size.

Should I enter the one-way or round-trip length?

Enter the one-way length from the source to the load. The single-phase formula multiplies by 2 to account for the current going out on one conductor and returning on the other, and the three-phase formula uses √3 for balanced loads. Entering the round-trip length doubles the result.

What voltage do I use for a three-phase circuit?

Use the line-to-line voltage, such as 208 V on a 208Y/120 V system or 480 V on a 480Y/277 V system, and the line current. If you are checking a single-phase circuit tapped line-to-neutral from a three-phase panel, such as a 120 V or 277 V circuit, select single-phase and that voltage.

Is voltage drop an NEC requirement?

Generally no. The 3 and 5 percent figures are in informational notes, and NEC 2023 90.5(C) states that informational notes are not enforceable requirements. Some specific articles do set mandatory limits, such as 647.4(D) for sensitive electronic equipment, and energy codes or project specifications can make a limit mandatory.

Why does the calculator use Table 8 and not Table 9?

NEC Chapter 9 Table 8 gives DC resistance at 75°C for every size and is the basis of most voltage drop calculations and of the K-factor shortcut. Table 9 gives AC resistance and reactance for conductors in PVC, aluminum, and steel conduit; for small branch-circuit conductors the two are close, while for large feeders in steel conduit Table 9 or manufacturer data is the better basis.

Try it on your own plans

Automate your electrical takeoffs and quotes.

Size the long runs here, then get more electrical quotes out with less time measuring and counting on PDF plans. BuildVision extracts counts and measurements from your plans and carries them through your rates and assemblies into a branded quote. Your team checks the quantities and pricing before sending. Try it free on your own plans.