A single-conductor building wire with thermoplastic insulation and a nylon jacket, rated 90°C in dry locations and pulled through conduit in commercial work.
THHN wire is a single insulated conductor, usually copper, with a thermoplastic (PVC) insulation and a nylon outer jacket. The letters stand for Thermoplastic, High Heat-resistant, Nylon-coated, and THHN is rated for 90°C in dry and damp locations. It is the standard building wire pulled through EMT and other raceways in commercial and industrial construction.
Most THHN sold today is dual-rated THHN/THWN-2, which adds a 90°C rating in wet locations, so the same wire can be used in underground conduit and outdoor runs. It is available in solid or stranded construction from 14 AWG up through 4/0 AWG and in kcmil sizes for feeders. Allowable ampacity is taken from NEC Table 310.16, and the final conductor size is often limited by terminal temperature ratings, conduit fill, and voltage drop rather than the 90°C insulation rating alone.
Drawings rarely show individual conductors. Panel schedules list breaker sizes and circuit numbers, homerun arrows and tick marks show the number of conductors in a run, and feeder schedules or riser diagrams call out sizes such as "4 #4/0 + 1 #4 G in 2-1/2 inch EMT." The specification (typically Division 26, section 26 05 19) sets the insulation type, copper versus aluminum, and the minimum branch-circuit size, often 12 AWG.
Estimators take off THHN in linear feet per conductor by size and color, then convert to the purchasing unit, since wire is commonly priced per 1,000 feet (often written as per M). The wire quantity for each run is the conduit length multiplied by the number of conductors, plus makeup length at every box, panel, and termination. Labor for pulling is usually carried per 1,000 LF by size and number of conductors pulled together.
The most common mistake is pricing conduit footage as wire footage and forgetting to multiply by conductor count, including the neutral and the equipment ground. Estimators also miss makeup and slack at panels and boxes, upsizing for voltage drop on long runs, and spec requirements for separate neutrals on multiwire circuits. Check the feeder schedule against the one-line diagram, take color-coding requirements into account when ordering, and apply a waste factor for reel ends that cannot be used.
THHN stands for Thermoplastic High Heat-resistant Nylon-coated. The T is the thermoplastic insulation, HH is the 90°C high-heat rating, and N is the nylon jacket that protects the insulation when the wire is pulled through conduit.
THHN is rated 90°C in dry and damp locations. THWN-2 is rated 90°C in wet locations as well. Most wire on the market is dual-listed as THHN/THWN-2, so in practice the same product covers both, but the estimator should confirm the listing when the specification calls for wet-location wire.
No. THHN is a single conductor without an outer protective sheath, so it must be installed in a raceway such as EMT, rigid conduit, or PVC, or inside equipment. For wiring without conduit, cable assemblies such as NM-B or MC cable are used instead.
It is measured in linear feet per conductor, by wire size, and usually purchased and priced per 1,000 feet. Multiply each conduit run length by the number of conductors in it and add makeup at both ends.