A variable air volume terminal unit that uses a motorized damper to vary the airflow delivered to a zone in response to its thermostat, often with a reheat coil.
A VAV box (variable air volume terminal unit) is a sheet metal box installed in the ductwork downstream of an air handler that controls how much conditioned air reaches one zone. A motorized damper, driven by a controller that reads the zone thermostat and an airflow sensor at the inlet, opens and closes to hold the zone at setpoint between a scheduled minimum and maximum airflow in CFM.
The basic types are single-duct cooling-only boxes, single-duct boxes with a hot water or electric reheat coil, and fan-powered boxes that add a small fan, arranged in series or in parallel with the primary air, to mix in plenum air. VAV systems are the most common HVAC arrangement in mid-size and large commercial office buildings because they let one central air handler serve many zones with different loads.
On mechanical plans each VAV box is shown at its location with a tag, such as VAV-2-07, and the mechanical schedule lists inlet size, maximum and minimum airflow, reheat type and capacity, and, for fan-powered units, fan airflow and electrical data. Controls drawings show the sequence of operations and the point list for each box, and the electrical drawings should show power for fan-powered and electric reheat units.
Estimators count VAV boxes each (EA), grouped by type and size from the schedule, and then carry the scope that every box drags with it: the inlet duct and transition, flexible or rigid outlet duct, sound attenuator if specified, hangers, hot water piping with a control valve and coil connection for hydronic reheat, controls wiring and a controller, power wiring where required, test and balance, and ceiling access. Many of these items fall in other trades or divisions, so the box count drives several parts of the estimate.
The most frequent mistake is pricing the box but missing the connected scope: reheat piping and valves, controls, electrical feeds for fan-powered and electric reheat units, and balancing. Estimators also miscount when the same box tag appears on both a floor plan and an enlarged plan, or when the schedule includes boxes on floors not shown in the drawing set. Reconcile the plan count against the schedule, check who furnishes the controller and the control valve, and confirm whether the mechanical or controls contractor carries the box-mounted controls.
A VAV box regulates the volume of supply air delivered to a zone. When the zone needs more cooling the damper opens, and when the zone is satisfied the damper closes toward its minimum airflow. Boxes with reheat can also add heat to that minimum airflow when the zone needs heating.
A standard VAV box has only a damper and controls. A fan-powered box adds a small fan that draws in return air from the ceiling plenum and mixes it with the primary air, which helps maintain air circulation and supports heating. Fan-powered boxes require electrical power for the fan.
They are shown on the mechanical floor plans with a tag and inlet and outlet duct connections, and their sizes and airflows are listed in the VAV box schedule. Controls and electrical drawings show their wiring and sequences.
Count them each by type and size from the plans and schedule, then add the associated ductwork, reheat piping, controls, electrical, balancing, and access requirements. Pricing the box alone usually understates the real cost of the scope.